Products  |  Thermodynamics, Heating and Sanitary Systems  |  Heating and Ventilation  |  HL 356
HL 356 Demo Unit, Gas Burner Show data sheet (pdf file)
Technical Description
The HL 356 demonstrates the basic functioning of an original gas burner and its typical behaviour in case of faults. Standard industrial components are used. All operating states of the burner are simulated, allowing this demo unit to be operated without gas and flames. The unit is therefore totally non-hazardous and has no gas or waste gas lines. On the front panel is a graphical representation of the controller unit connection. Important electrical monitoring points (controller unit terminals) on the burner are accessible for fault analysis using laboratory sockets and bridges on the front panel. Faults can thus be checked either during operation under voltage or with no voltage as an isolated component.  
Learning Objectives / Experiments

- Specification of boiler temperature setpoint
  (thermostat) using potentiometer; display of boiler
  water temperature
- Specification of boiler water temperature using
  potentiometer
- Representation of flame aspect and burner
  operating state displays
- Possible defects (resolved using fault switch): 
  + air pressure control device

  + boiler temperature controller

  + flame safeguard

  + gas solenoid valve

  + fan motor

  + gas pressure control device

  + safety temperature limiter

  + ignition transformer

  + current supply controller unit

Features
* Electronic simulation of the operation of a forced air
  gas burner1
* PLC controlled simulation of 9 faults on individual
  components
Alternative products
HL 358 -- Forced Air Gas Burner Training Panel
HL 500 -- Instantaneous Gas Heater
Specification

[1] Simulation model of an forced air burner mounted on a mobile trolley
[2] Simulation of all burner operating states
[3] Fault simulation: 9 fault switches in lockable box
[4] Additional actual system components: flame safeguard, gas pressure and air pressure control devices, ignition transformer, thermostat, safety temperature limiter, gas solenoid valves, fan motor, heater emergency switch
[5] Burner buttons positioned on front panel
[6] Important electrical monitoring points on burner accessible via laboratory sockets and measuring bridge connectors for fault analysis
[7] 230V, 50Hz, 1 phase

 

Technical Data

Fully automatic air forced gas burner for natural gas

- power: 15...45kW

- connection load: approx. 160W

- motor power: 70W
PLC:

- 16 digital inputs

- 14 digital outputs

- 2 analogue inputs

- 1 analogue output
Digital multimeter: for direct or alternating voltage

 

Dimensions and Weight
l x w x h : 1250 x 700 x 1650 mm
Weight : approx. 105 kg
Connections
230V, 50Hz, 1 phase
Scope of Delivery

1 demo unit

1 LCD digital multimeter

2 measuring lines

1 instruction manual

1 gas burner manual

Order Details
065.35600  HL 356  Demo Unit, Gas Burner
© 2005 G.U.N.T. Gerätebau GmbH