Products  |  Thermodynamics, Heating and Sanitary Systems  |  Refrigeration and Air Conditioning  |  ET 605
ET 605 Recirculating Air Conditioning Trainer Show data sheet (pdf file)
Technical Description

Air conditioning is a central aspect of building technology. Therefore air conditioning is a major element when training building craftsmen and engineers.
The clear arrangement of the model ET 605 presents a complete air conditioning system with a transparent ventilation duct and a climatic chamber. The key elements of the system are a cooler with refrigeration system, blower, vapor humidifier and a heater. Three motorized air flaps control the distribution of air within the system. The climatic chamber is provided with two different heating loads (damp and dry). Temperature and relative humidity are measured at relevant points in the ventilation duct and are displayed digitally. In the refrigerating circuit two pressure gauges with integral temperature scales and a flow rate meter supply all relevant measured values. 
The ET 605 is manually operated. An important feature of the system is that it is fully prepared for attaching various automation solutions. The user can thus include this important topic as part of the instruction. The following solutions are available:
- Software solution ET 605.01

- Industrial climatic controller ET 605.02

- Signal connection box ET 605.03 for connecting an individual

application solution.

 

The well-structured instructional material sets out the technological fundamentals and provides a step-by-step guide through the experiments.

 

Learning Objectives / Experiments

- Familiarization with an air conditioning system and

  its components
- Conditioning the air within a room
- Mixing different airflows
- Representation of the humidification and 

  dehumidification of air using a h-ω diagram
- Representation of the refrigerant circuit using a
  p-h phase diagram
- Effects of a heating load (damp and dry)
- Recirculation and fresh air modes
 
together with the optional accessory:
- Automation of an air conditioning system

Features

* Climate chamber with latent and sensible heat

  sources as heating loads1
* Recirculation and fresh air modes1
* Optional PC data acquisition in ET 605.011

* Connection facilities for using various automation

  solutions

Available accessories
ET 605.01 -- PC Data Acquisition with Software Controller
ET 605.02 -- HVAC System Controller
ET 605.03 -- I/O Connection Box
Alternative products
ET 600 -- Open Duct Air Conditioning Trainer
ET 611 -- Air Conditioning System with Climate Chamber
ET 915 -- Base Condensing Unit
Overview
ET 605 Recirculation Air Conditioning Trainer
Specification

[1] Model of an air conditioning system with recirculation and fresh air modes
[2] Transparent ventilation duct with blower, air cooling, humidifier, flaps, heater, sensors; available duct cross-section 155x155mm
[3] Chamber with damp (latent) and dry (sensible) heat source as cooling load
[4] Motorized flaps for recirculation and fresh air modes
[5] System diagram with indicator lamps
[6] System prepared for various automation solutions: 4 data cable connections for linking in accessories
[7] Refrigerant R134a, CFC-free
 

Technical Data

Air-cooled condenser (refrigeration system)
- power consumption: 140W at -10°C
- refrigeration power: 320W at +5/40°C
Humidifier
- heating power: 400W
Duct heater
- heating power: 360W
2 heaters in the chamber
- power: 0...250W each, continuously variable
 

Measuring ranges
- temperature: 0...50°C
- humidity: 10...90% r.H.
- power: 0...2500W (compressor power consumption

  in the refrigeration system); 2x 0...300W (latent and

  sensible cooling load)
- pressure in the refrigeration circuit: -1...9bar /

  -1...24bar
- temperature scale in the pressure gauge:  

  -60...80°C
- refrigerant flow rate: 1.5...23.5 L/h

 

Dimensions and Weight
l x w x h : 2000 x 750 x 1900 mm
Weight : approx. 160 kg
Connections

230V, 50/60Hz, 1 phase or 230V, 60Hz, 3 phase
Cold water supply

Scope of Delivery

1 air conditioning system, fully assembled and filled

   with refrigerant

1 instruction manual

Order Details
061.60500  ET 605  Recirculating Air Conditioning
                    Trainer