Technical Description
The ET 405 contains a hermetic compressor, 4 heat exchangers, 3 expansion valves and 4 different interchangeable capillaries. The unit can be operated in different modes. 11 manually operated valves allow corresponding changes to be made to the refrigeration circuit. The relevant measured values are displayed directly on indicator instruments. Therefore, sequences and consequences of switching operations within a cooling unit can be directly investigated. Sight glasses in the refrigerant circuit allow direct observation of the refrigerant status. A coaxial tube bundle heat exchanger can be operated as a counterflow condenser or as a parallel flow evaporator. This heat exchanger is used to heat or cool a glycol/water mixture circuit. Refrigerating loads are created by different fan speeds on the finned tube evaporators.
Learning Objectives / Experiments
- Layout, function and main components of a heat
  pump 
- Measurement of relevant pressures, temperatures,
  flow rates, current and voltage
- Illustration of the thermodynamic cyclic process in a
  p-h state diagram
- Comparison of different operating modes
- Comparison of different expansion elements
  (expansion valve, 4 capillaries)
- Determination of: efficiency, coefficient of
  performance, specific compressor work,
  compressor pressure ratio, specific cooling capacity
  and specific refrigerating capacity
- Heat balance
Features
* Air-to-water heat pump
* Heating and cooling
* High practical relevance due to use of standard
  refrigeration engineering components
* 7 different modes, adjustable using 11 manually
  operated valves
Alternative products
ET 103 -- Heat Pump with Pumpdown Control
ET 104 -- Heat Pump with Dual Mode Evaporator
ET 422 -- Commercial Refrigeration Unit with Fault Simulation
Specification
[1] Air-to-water heat pump for cooling and heating
[2] 7 different operating modes possible, adjustable using 11 manually operated valves
[3] Hermetic piston compressor, finned tube condenser, 2 finned tube evaporators
[4] Coaxial tube heat exchanger (refrigerant - water/glycol)
[5] Water/glycol circuit with 3.5ltr tank and circulating pump
[6] Refrigeration circuit with intake pressure regulator, sight glasses, pressure regulators, 3 thermostatic expansion valves, 4 different capillary tubes
[7] CFC-free refrigerant R134a
[8] 230V, 50/60Hz, 1 ph. or 120V, 60Hz, 1 ph.
Technical Data
Compressor: power consumption 235W at
-10°C, refrigerating capacity: 580W at 5/32°C
Tube heat exchanger for R134a: Power: 1.6kW at
0°C, Δt=6K
Finned tube evaporator with fan: heat exchanger surface: 0.55m², power: 470W
Finned tube condenser with fan: heat exchanger surface: 1m², power: 750W
Capillary lengths: 300-500-1000-1500mm
Dimensions and Weight
l x w x h : 1700 x 750 x 1600 mm
Weight : approx. 185 kg
Connections
230V, 50/60Hz, 1 phase or 120V, 60Hz, 1 phase
Scope of Delivery
1 heat pump, complete, 3 capillaries 1 stopwatch, 1 graduated beaker, 2ltr, 1 combination wrench AF17, 1 pressurised air hose, 2m with hose clips (for filling tank), 1 instruction manual
Order Details
061.40500  ET 405  Reverse Cycle Refrigeration Training System